CONTROLS SETUP CHECKLIST AND CONFIGURATION LOG
RECORD ALL SETPOINTS AND CONFIGURATIONS LISTED BELOW FOR FUTURE REFERENCE
*Default will be different depending on unit size.
MODEL NUMBER Software Version
SERIAL NUMBER MBB CESR131343--
DATE: ECB1 CESR131249--
TECHNICIAN ECB2 CESR131249--
NAVI CESR131227--
SCB CESR131226--
CEM CESR13174--
MARQ CESR131171--
SUBMODE
SUB
SUBMODE
ITEM SETTING
UNITS FACTORY DEFAULT
RANGE
ENGLISH
ITEM EXPANSION COMMENTS CCN TABLE
CCN POINT
NAME
English Metric VAV CV
UNIT
UNIT Unit Configurations Overall Unit Configurations
CTL.T — — 4 1
1=VAV RAT,
2=VAV SPT
3=TSTAT MULTI,
4=TSTAT 2STAGE,
5=SPT MULTI,
6=SPT 2STAGE
Unit Control Type Used to select the type of capacity control UNIT CTRLTYPE
SIZE TONS TONS 20 * 20 *
20,25,27,30,35,
40,50,60
20,25,27,30,35, 40,50,60 used to select the nominal size unit UNIT SIZE
S.MLV — — NO NO NO/YES Minimum Load Valve? Used to enable the minimum load valve option COOL_CFG MLV_SEL
VS.FN — — NO YES NO/YES Variable Speed Fan? used to enable inverter fan speed control UNIT VARSFAN
IF.M — — NONE NONE
0=NONE, 1=SWITCH,
2=DELTA PRESS
Fan Status Monitoring Type
used to configure the type of fan status monitor.
Delta pressure only avaliable on VAV units
SFS_WORK SFS_MON
IF.IS — — NO NO YES/NO Fan Fail Shuts Down Unit
Action taken if a fan failure is dectected FAN.S
swtch
SFS_WORK SFS_SHUT
S.MM — — NO NO YES/NO MotorMaster Installed?
Used to configure unit to allow for the use of
MotorMaster V
UNIT MM_SEL
DELY MIN MIN 0 0 0 TO 15 Minutes off time time unit is off before next start UNIT DELAY
MAT.S — — YES YES YES/NO Estimate MAT?
enable routine to estimate mixed air temp,
Should be set to yes
UNIT,
ECONDIAG
MAT_SEL
R.MAT — — NO NO YES/NO Reset MAT Table Used to reset the mixed air temperaturre table EDT_WORK RSETMATT
DP.XR — — NO NO YES/NO Disch. Press. Transducer not available at this time UNIT DP_TRANS
FAN.M X X 0 0 0,1 Fan Mode (0=Auto, 1=Cont)
Used to configure fan operation during occupied
periods
CONFIG FANM
SAMP SEC SEC 60 60 0 TO 720 VAV Unocc.Fan Retry Time
This controls the sample rate for checking the
return air temperature by turing on the fan while
in the unccupied mode.
CONFIG SAMPMINS